The two-wire transmitter acquires the temperature through an RTD temperature probe or a thermocouple. For RTD temperature probes, the probe can be connected in a two-wire circuit, three-wire circuit, or four-wire circuit. The dTRANS T01 Ex is designed for mounting in a potentially explosive area.
general technical data | |
---|---|
Ambient temperature | -40 to +85 °C |
Voltage supply | DC 11.5 to 30 V |
RTD temperature probe input | Pt100, Pt500, Pt1000 (Junior only Pt100/Pt1000), two-wire/three-wire/four-wire circuit |
Installation | In terminal head, type B |
Installation | On mounting rail/DIN rail 35 × 7.5 mm |
Special features | Customer-specific linearization |
Output | 4 to 20 mA |
Configuration | Via PC interface, HART® version via HART® modem |
Output | 4 to 20 mA (invertible) |
NAMUR compliant | NE21 |
Approval | ATEX/IECEx |
Calibration accuracy | ± 0.05 % |
Galvanic isolation | 3.75 kV, 2 kV, 1 kV |
Configuration | Via HART® modem |
Voltage supply | DC 11.5 to 30 V (two-wire transmitter) |
Galvanic isolation | 2 kV |
RTD temperature probe input | Pt100, Pt500, Pt1000, two-wire/three-wire/four-wire circuit |
Thermocouple input | J, K (more upon request) |
Thermocouple input | L, J, U, T, K, E, N, S, R, B, D, C (Junior only J, K, N, S, R) |
Ambient temperature | -25 to +70 °C |
No related documents found.